DODOMACH PNEUMATIC

FLUID VALVE

Electric Two-Way Brass Regulating Valve

Electric two-way brass regulating valve, DN15-DN80, with stainless steel stem, NBR seal and multiple control-package options.

Dimensions and Structure

Electric Two-Way Brass Regulating Valve dimensions

Electric Two-Way Brass Regulating Valve

Electric two-way brass regulating valve for heating and air-conditioning control applications. The source lists DN15-DN80 sizes and on/off, modulating and differential-pressure control packages. Dimensions, valve service data and the reference actuator specifications are presented separately.

Dimensions

DN L (mm) D (mm) A (mm) H (mm)
15 83 94 46.5 233
20 83 94 46.5 233
25 103 94 56 237
32 110 94 50 242
40 122 94 50 244
50 131 94 57 249
65 161 94 71 258
80 180 94 83 260

Materials and Service

Parameter Specification
Body, cover and disc Brass
Stem Stainless steel
Seal NBR
Medium Hot or cold water;50% ethylene glycol
Medium temperature 5-95 C
Nominal pressure 1600 kPa
Flow characteristic options Equal percentage or linear
Leakage stated in source 0.01% of Kv

Reference 24 VAC Actuator

Parameter Specification
Rated supply 24 VAC +/-10%;50/60 Hz
Voltage control signal 0-10 VDC
Voltage feedback signal 0-10 VDC
Output force 600 N
Full-stroke time 180 seconds
Actuator weight 0.8 kg
Operating ambient -5 to55 C
Housing Flame-retardant ABS engineering plastic

Control Package Options

Package Supply options Additional equipment listed
On/off, two-piece set 220 VAC or24 VAC Not listed
Modulating, two-piece set 220 VAC or24 VAC Not listed
Differential-pressure, four-piece set 24 VAC Differential-pressure device; transformer
Modulating, five-piece set 24 VAC Transformer; sensor; temperature controller

The actuator table describes the24 VAC reference configuration only; it does not specify the220 VAC package ratings. Power consumption is omitted because the source gives an inconsistent unit. The technical table lists0-10 mA signals, while the wiring illustration also shows4-20 mA notation; confirm the required signal range before selection. No numeric Kv schedule or connection thread standard is supplied. Package equipment is listed for selection and is not a statement that every accessory is included with the pictured valve.