Dimensions and Structure

Self-Operated Dynamic Flow Balancing Valve
Self-operated dynamic flow balancing valve for circulating-water systems. A manual setting establishes the required flow while the valve responds to pressure variations without an external power supply.
Source-Listed Dimensions and Flow Ranges
| DN | L (mm) | H (mm) | Flow control range (m3/h) |
|---|---|---|---|
| 15 | 110 | 142 | 0.1-1 |
| 20 | 110 | 142 | 0.1-1.5 |
| 25 | 156 | 142 | 0.2-2 |
| 32 | 210 | 180 | 0.5-4 |
| 40 | 210 | 235 | 1-6 |
| 50 | 215 | 235 | 2-10 |
| 65 | 230 | 258 | 3-15 |
| 80 | 280 | 296 | 5-25 |
| 100 | 300 | 337 | 10-35 |
| 125 | 315 | 391 | 15-50 |
| 150 | 350 | 405 | 30-80 |
| 200 | 405 | 525 | 40-180 |
| 250 | 455 | 585 | 100-300 |
| 300 | 610 | 650 | 150-500 |
| 350 | 640 | 730 | 200-700 |
| 400 | 740 | 850 | 275-900 |
Operating Information
| Parameter | Specification |
|---|---|
| Function | Self-operated flow regulation with manual flow setting |
| External power | Not required |
| Nominal pressure | 1.6 MPa |
| Working differential pressure | 0.02-0.3 MPa |
| Application | Water circulation in heating, cooling and air-conditioning systems |
| Body and trim materials | Configuration confirmation required |
| Medium temperature | Configuration confirmation required |
| Connection | Illustrated configuration is flanged; confirm connection for selected size |
The source lists conflicting body/trim materials and medium-temperature ranges, so those ratings require confirmation for the selected configuration. The photograph and structure drawing show a flanged configuration; confirm connection details for the selected size. Dimensions are transcribed from the source table, including the merged H value for DN15-DN25. No flange standard or unlisted bolt dimensions are inferred.