Dimensions and Structure

Cast Steel Flanged Gas Emergency Shutoff Valve
Cast steel flanged gas emergency shutoff valve with an electrical trip mechanism and manual reset knob. The described normally-open configuration closes when electrically triggered and remains locked until reset.
Flanged Configuration Dimensions
| DN | L (mm) | W (mm) | H (mm) |
|---|---|---|---|
| 25 | 160 | 115 | 237.5 |
| 32 | 180 | 135 | 267.5 |
| 40 | 200 | 145 | 272.5 |
| 50 | 225 | 160 | 300 |
| 65 | 225 | 180 | 345 |
| 80 | 285 | 195 | 417.5 |
| 100 | 330 | 215 | 487.5 |
| 125 | 400 | 245 | 527.5 |
| 150 | 400 | 280 | 598 |
| 200 | 460 | 335 | 697.5 |
| 250 | 600 | 390 | 795 |
| 300 | 700 | 440 | 870 |
| 350 | 800 | 550 | 1025 |
Materials
| Component | Material |
|---|---|
| Body | Cast steel |
| Cover | Stainless steel |
| Disc | Stainless steel |
| Stem | Stainless steel |
| Seal | NBR |
Operation and Configuration
| Parameter | Specification |
|---|---|
| Connection | Flanged |
| Structure | Direct acting |
| Normal operating state | Normally open; coil de-energized during normal service |
| Trip operation | Electrical pulse-triggered closure with self-locking |
| Reopening | Manual reset for the described normally-open configuration; confirm selected reset arrangement |
| Nominal pressure listed in source | 1.6 MPa |
| Working differential pressure listed in source | 0-0.05 MPa |
| Closing time listed in source | Less than 1 second |
| Intended gases listed in source | Coal gas, natural gas and LPG; confirm gas compatibility for the selected configuration |
| DC supply options listed in source | 24 V DC or 12 V DC; specify selected option |
| Temperature rating | Requires configuration confirmation |
| Explosion protection | Certification and exact rating require confirmation; no certification is asserted |
Dimensions shown are for the flanged configuration only. Nominal body pressure and working differential pressure are different ratings and must not be treated as interchangeable. Confirm the selected gas, supply voltage, reset arrangement, temperature limits and applicable certification before specifying the valve. Source temperature statements conflict, and an exact explosion-protection classification is not provided; neither is asserted here. Installation and commissioning require qualified personnel and the approved documentation for the selected assembly.