Dimensions and Structure

Capillary Temperature Controller
Mechanical temperature controller with a remote sensing bulb and capillary tube. Its SPDT contact changes state according to the selected temperature setting and the temperature sensed by the bulb.
Range and Sensing Bulb Selection
| Catalog reference | Setting range (°C) | Factory ON (°C) | Factory OFF (°C) | Maximum bulb temperature (°C) | Bulb length × diameter (mm) | Installation condition |
|---|---|---|---|---|---|---|
| TS30 | −30 to 0 | −19 | −14 | 45 | 80 × Ø10 | Body warmer than bulb |
| TS15 | −15 to +15 | −5 | 0 | 45 | 80 × Ø10 | Body warmer than bulb |
| TS40 | 0 to 40 | 17 | 20 | 70 | 120 × Ø12 | No relative body/bulb temperature condition stated |
| TS90 | 40 to 90 | 55 | 60 | 120 | 120 × Ø12 | No relative body/bulb temperature condition stated |
| TS120 | 70 to 120 | 90 | 95 | 130 | 120 × Ø12 | No relative body/bulb temperature condition stated |
General Specifications
| Item | Value |
|---|---|
| Ambient temperature | −20 to +70 °C |
| Cable-entry hole diameter | 15 mm |
| Standard capillary length | 1 m |
| Contact arrangement | SPDT |
| Terminal 1 | Common |
| Terminals 1–3 | Close on temperature rise |
| Terminals 1–5 | Close on temperature fall |
Electrical Ratings
| Load | 110 V AC | 220 V AC |
|---|---|---|
| Non-inductive | 20 A | 10 A |
| Inductive, full load | 15 A | 8 A |
| Inductive, instantaneous | 72 A | 72 A |
Drawing Dimensions
| Feature | Dimension (mm) |
|---|---|
| Housing width | 80 |
| Housing depth | 49 |
| Housing height shown | 62.8 |
| Mounting projection shown | 2.4 |
| Upper mounting offset shown | 20.5 |
| Mounting spacing shown | 25 |
Select the temperature range, bulb dimensions and maximum bulb temperature. For TS30 and TS15, the controller body must remain warmer than the sensing bulb. The supplied catalog identifies automatic and manual-reset contact arrangements; specify the required reset version. The sensing bulb maximum temperature is a limit, not an additional control range.