Dimensions and Model Identification
LFM33
LFM73
Digital Differential Pressure Transmitter and Controller
Digital differential pressure instruments combining local indication with selectable transmitter, relay and audible-alarm functions. Designed for air or neutral gas monitoring and control in ventilation systems, filter monitoring and cleanrooms. Select output and control options independently; relay contacts are not included in every configuration.
Model Selection
| Catalog series | Medium | Range options (Pa) | Accuracy | Display | Supply |
|---|---|---|---|---|---|
| LFM33 | Air or neutral gas | ±100 / ±1000 / ±10000 | ±1% FS | 76 × 33 mm LCD | 16–30 VDC |
| LFM73 | Air or neutral gas | ±100 / ±1000 / ±10000 | ±1% FS | Four-digit 0.8-inch LED | 16–30 VDC or 24 VAC ±20% |
Range Selection
| Series | Range code | Range (Pa) |
|---|---|---|
| LFM33 | 6 | −100 to +100 |
| LFM33 | 0 | −1000 to +1000 |
| LFM33 | 2 | −10000 to +10000 |
| LFM73 | 6 | −100 to +100 |
| LFM73 | 0 | −1000 to +1000 |
| LFM73 | 2 | −10000 to +10000 |
Transmitter Output Options
| Series | Output code | Output |
|---|---|---|
| LFM33 / LFM73 | N | No transmitter output |
| LFM33 / LFM73 | E | RS485, Modbus RTU |
| LFM33 / LFM73 | A | 4–20 mA and 0–10 V |
| LFM73 | H | 4–20 mA and RS485 |
Control and Alarm Options
| Series | Control code | Configuration |
|---|---|---|
| LFM33 | N | No control output |
| LFM33 | R | Two SPDT relays plus buzzer |
| LFM33 | B | Buzzer only |
| LFM33 | D | Two SPDT relays |
| LFM73 | N | No control output |
| LFM73 | R | Two relays plus buzzer; contact form requires confirmation |
| LFM73 | B | Buzzer only |
| LFM73 | D | Two relays; contact form requires confirmation |
Panel and Pressure Entry Options
| Series | Option | Code | Configuration |
|---|---|---|---|
| LFM33 | Panel | P | Round plastic panel |
| LFM33 | Panel | S | Rectangular stainless steel panel |
| LFM73 | Panel | P | Plastic panel |
| LFM33 | Pressure entry | F | Front |
| LFM33 | Pressure entry | B | Rear |
| LFM33 | Pressure entry | S | Side |
| LFM73 | Pressure entry | F | Front |
| LFM73 | Pressure entry | B | Rear |
| LFM73 | Pressure entry | S | Side |
Operating Specifications
| Parameter | LFM33 | LFM73 |
|---|---|---|
| Operating temperature | −10 to +60 °C | −20 to +80 °C |
| Compensation temperature | −10 to +60 °C | −10 to +60 °C |
| Storage temperature | −20 to +70 °C | −40 to +85 °C |
| Protection | IP65 | IP65 |
| Pressure connection | Ø6.5 mm recessed port | Ø6.5 mm recessed port |
| Power consumption | ≤2.5 W | ≤1.5 W |
| Relay rating (relay options) | 3 A at 250 VAC / 30 VDC | 3 A at 250 VAC / 30 VDC; confirm contact form |
| Response time | Confirm configuration | 0.5 s default; 1 / 2 / 4 s selectable |
| Weight | 360 g | 390 g |
Dimensions
| Series / panel | Face dimensions (mm) | Body dimensions (mm) | Notes |
|---|---|---|---|
| LFM33 round | Ø135 | Ø115; depth35 | LCD76×33; Ø6.5 ports |
| LFM33 rectangular | 180×130 | Depth38 | Mounting spacing150×100 |
| LFM73 round | Ø121 | Ø113.5; overall depth42 | Body depth36.9; mounting circleØ104.9 |
Select the series, range, transmitter output, control output, panel and pressure-entry configuration. LFM33 supports two SPDT relays when the relay option is selected. Confirm the LFM73 relay contact arrangement before wiring or ordering, because supplier ordering and technical tables differ. Confirm model-specific overload limits. The LFM73 photograph shows an H-output label and does not demonstrate that relays are installed.
All drawing dimensions are in millimetres.