Dimensions and Structure

Temperature and Humidity Controller
Indoor temperature and relative-humidity controller with a backlit display and local setting buttons. Select relay switching, buzzer/LED alarms, or both for environmental monitoring and control in equipment rooms, buildings and storage areas, with voltage, digital or passive temperature signal options.
Measurement Specifications
| Item | Specification |
|---|---|
| Humidity sensor | Digital |
| Humidity range | 0–100% RH |
| Humidity accuracy | ±3% RH at 20 °C and 20–80% RH |
| Response time | ≤10 s at 20 °C in slowly moving air |
| Temperature sensor | Digital or selected passive resistance element |
| Temperature ranges | 0–50 °C or −20–60 °C; other ranges by confirmation |
| Digital temperature accuracy | ±0.3 °C at 20 °C |
| Measurement outputs | 0–10 VDC or RS485/Modbus; selected passive temperature options |
Control, Alarm and Supply
| Item | Specification |
|---|---|
| Relay configuration | 2 × SPST |
| Relay rating | 3 A at 30 VDC; 3 A at 250 VAC |
| Alarm devices | 1 buzzer and 1 LED, according to selected option |
| Supply | 15–35 VDC or 24 VAC ±20% |
| AC supply requirement | Isolation transformer required |
| Voltage-output load | ≥10 kΩ |
| Local interface | Backlit LCD, units and setting buttons |
| Display increment | 0.1 °C and 0.1% RH |
Operating Conditions and Dimensions
| Item | Specification |
|---|---|
| Working environment | −20 to +60 °C; 5–95% RH, non-condensing |
| Protection | IP30 |
| Width × height | 86 × 115 mm |
| Overall depth | 27.5 mm |
| Body depth shown | 26.5 mm |
| Rear mounting spacing | 60 mm horizontal; 38 mm vertical |
Selection Fields
| Field | Code | Option |
|---|---|---|
| Humidity output | V10 / RS | 0–10 VDC / RS485-Modbus |
| Temperature output | V10 / RS | 0–10 VDC / RS485-Modbus |
| Passive temperature | 0 / 1 | Pt1000 / Pt100; ±0.2 °C at 0 °C |
| Passive temperature | 2 / 3 | NTC20k / NTC10k; ±0.4 °C at 25 °C |
| Temperature range | 0 / 1 / 2 / 8 | None / 0–50 °C / −20–60 °C / custom |
| Display and keys | 1 | LCD with backlight and keys |
| Alarm/relay option | 1 | Alarm only |
| Alarm/relay option | 2 | Relay only |
| Alarm/relay option | 3 | Alarm and relay |
Specifications and drawing apply to the selected indoor configuration. Select humidity and temperature signals, temperature sensor, calibrated range and alarm/relay option. Use temperature range code 1, 2 or 8 only with the V10 temperature output; other temperature-output options use code 0 according to the catalog. Confirm relay assignments, switching thresholds, hysteresis, load type and wiring for the delivered unit. Prolonged exposure to concentrated chemical gases may shift sensor readings. Other high-temperature or separate-probe versions require their own configuration data.