Air velocity transmitter using an external pitot pickup and micro-pressure sensing for air or neutral gas. An LCD indicates the measured velocity, with a selected current, voltage or RS485 output for ventilation and process monitoring.
Specifications below describe the LFS71 single-output configuration. The 0–40 m/s option requires an L-type pitot tube and is not established by the illustrated pickup.
Measurement and Operating Specifications
| Item | Specification |
|---|---|
| Medium | Air or neutral gas |
| Measurement method | Pressure-derived air velocity with external pitot pickup and MEMS micro-pressure sensing |
| Standard ranges | 0–10, 0–20, 0–30 or 0–40 m/s |
| Accuracy | ±3.0% FS for air velocity >3 m/s |
| Allowable overpressure | 10 kPa |
| Host operating temperature | −20 to +80 °C |
| Probe operating temperature | −40 to +450 °C |
| Compensated temperature range | −10 to +60 °C |
| Host storage temperature | −40 to +85 °C |
| Response settings | 0.5 s default; 1 s, 2 s or 4 s |
| Housing protection | IP65 |
| Display | Digital LCD |
| Supply | 12–30 VDC or 24 VAC ±20% |
| Power consumption | ≤1.5 W |
| Housing material | Cast aluminium |
| Host weight, approximate | 1238 g |
Range Selection
| Code | Range | Condition |
|---|---|---|
| 1 | 0–10 m/s | Select compatible pickup |
| 2 | 0–20 m/s | Select compatible pickup |
| 3 | 0–30 m/s | Select compatible pickup |
| 4 | 0–40 m/s | L-type pitot tube only |
| X | Custom | Confirm required range and pickup |
Single-Output Selection
| Code | Output |
|---|---|
| A | 4–20 mA |
| B | 0–10 VDC |
| C | RS485; Modbus RTU |
Host Dimensions
| Item | Value |
|---|---|
| Overall width shown | 179 ±2 mm |
| Horizontal mounting spacing | 124 ±1 mm |
| Overall height shown | 168 ±2 mm |
| Vertical mounting spacing shown | 144.7 ±1 mm |
| Side-view depth | 92.5 ±1 mm |
| Body diameter shown | 104 mm |
| Cable entry marking | M20 ×1.5 |
| Lower width shown | 120 mm |
Dimensions Drawing
Ordering Information
Specify the LFS71 configuration, range code, single-output code and compatible pickup. Confirm the complete ordering designation, pressure connections and tubing for the application.
Select the velocity range, output and compatible pickup together. The 0–40 m/s range requires an L-type pitot tube; the illustrated pickup does not establish that option. The stated accuracy applies above 3 m/s. Keep the host within its own temperature range: the higher probe temperature rating does not apply to the transmitter enclosure. An isolated AC source is recommended when using AC power. Confirm pressure connection size and tubing before installation. Specifications and host drawing describe the single-output configuration; dual-output versions require their own code and dimensions. Hazardous-area suitability is not established by this product page.