DODOMACH PNEUMATIC

Temperature & Humidity Sensors

Temperature and Humidity Controller

Indoor temperature and relative-humidity controller with a backlit display and local setting buttons. Select relay switching, buzzer/LED alarms, or both for environmental monitoring and control in equipment rooms, buildings and storage areas, with voltage, digital or passive temperature signal options.

Dimensions and Structure

Temperature and Humidity Controller dimensions

Temperature and Humidity Controller

Indoor temperature and relative-humidity controller with a backlit display and local setting buttons. Select relay switching, buzzer/LED alarms, or both for environmental monitoring and control in equipment rooms, buildings and storage areas, with voltage, digital or passive temperature signal options.

Measurement Specifications

Item Specification
Humidity sensor Digital
Humidity range 0–100% RH
Humidity accuracy ±3% RH at 20 °C and 20–80% RH
Response time ≤10 s at 20 °C in slowly moving air
Temperature sensor Digital or selected passive resistance element
Temperature ranges 0–50 °C or −20–60 °C; other ranges by confirmation
Digital temperature accuracy ±0.3 °C at 20 °C
Measurement outputs 0–10 VDC or RS485/Modbus; selected passive temperature options

Control, Alarm and Supply

Item Specification
Relay configuration 2 × SPST
Relay rating 3 A at 30 VDC; 3 A at 250 VAC
Alarm devices 1 buzzer and 1 LED, according to selected option
Supply 15–35 VDC or 24 VAC ±20%
AC supply requirement Isolation transformer required
Voltage-output load ≥10 kΩ
Local interface Backlit LCD, units and setting buttons
Display increment 0.1 °C and 0.1% RH

Operating Conditions and Dimensions

Item Specification
Working environment −20 to +60 °C; 5–95% RH, non-condensing
Protection IP30
Width × height 86 × 115 mm
Overall depth 27.5 mm
Body depth shown 26.5 mm
Rear mounting spacing 60 mm horizontal; 38 mm vertical

Selection Fields

Field Code Option
Humidity output V10 / RS 0–10 VDC / RS485-Modbus
Temperature output V10 / RS 0–10 VDC / RS485-Modbus
Passive temperature 0 / 1 Pt1000 / Pt100; ±0.2 °C at 0 °C
Passive temperature 2 / 3 NTC20k / NTC10k; ±0.4 °C at 25 °C
Temperature range 0 / 1 / 2 / 8 None / 0–50 °C / −20–60 °C / custom
Display and keys 1 LCD with backlight and keys
Alarm/relay option 1 Alarm only
Alarm/relay option 2 Relay only
Alarm/relay option 3 Alarm and relay

Specifications and drawing apply to the selected indoor configuration. Select humidity and temperature signals, temperature sensor, calibrated range and alarm/relay option. Use temperature range code 1, 2 or 8 only with the V10 temperature output; other temperature-output options use code 0 according to the catalog. Confirm relay assignments, switching thresholds, hysteresis, load type and wiring for the delivered unit. Prolonged exposure to concentrated chemical gases may shift sensor readings. Other high-temperature or separate-probe versions require their own configuration data.