Temperature & Humidity Sensors

Temperature and Humidity Transmitter

Combined temperature and relative-humidity transmitter for HVAC, equipment rooms, buildings and storage areas. Wall-mounted, duct-mounted and separate-probe arrangements are available with selected current, voltage or RS485/Modbus outputs and optional local LCD indication.

Dimensions and Structure

Temperature and Humidity Transmitter dimensions

Temperature and Humidity Transmitter

Combined temperature and relative-humidity transmitter for HVAC, equipment rooms, buildings and storage areas. Wall-mounted, duct-mounted and separate-probe arrangements are available with selected current, voltage or RS485/Modbus outputs and optional local LCD indication.

Humidity and Temperature Measurement

Item Specification
Humidity sensor Digital
Humidity range 0–100% RH
Humidity accuracy ±3% RH at 20 °C and 20–80% RH
Humidity response time ≤10 s at 20 °C in slowly moving air
Temperature sensor Digital sensor or selected passive resistance element
Temperature range options 0–50 °C or −20–60 °C; other ranges by confirmation
Digital temperature accuracy ±0.3 °C from 0 to 60 °C
Mounting options Wall, duct or separate probe

Output and Power Supply

Configuration Signal Supply
Current 4–20 mA, two-wire 19.5–35 VDC at 500 Ω; 9.5–35 VDC at 0 Ω
Voltage 0–10 VDC, three-wire 15–35 VDC or 24 VAC ±20%
Digital RS485/Modbus 15–35 VDC or 24 VAC ±20%

Operating Conditions

Item Specification
Current output load ≤500Ω
Voltage output load ≥2kΩ
Operating environment −20 to +60 °C; 5–95% RH, non-condensing
Protection IP65
Display Optional LCD with units;4–20mA version without backlight
AC supply Isolated supply required

Passive Temperature Options

Code Element Accuracy
0 Pt1000 ±0.2 °C at 0 °C
1 Pt100 ±0.2 °C at 0 °C
2 NTC20kΩ ±0.4 °C at 25 °C
6 NTC10kΩ ±0.4 °C at 25 °C

Selection Fields

Field Options
Accuracy code 3:±3% RH; temperature accuracy depends on sensor
Humidity output V10:0–10VDC;A4:4–20mA;RS:RS485/Modbus
Temperature output V10,A4,RS or selected passive element
Temperature range code 0:none;1:0–50°C;2:−20–60°C;8:custom
Display code 0:none;1:LCD

Catalog Dimensions

Configuration Dimension Value(mm)
Wall Enclosure width/height/depth 100/80/46
Wall Overall height 169
Wall Probe diameter 15
Duct Enclosure width/height/depth 100/80/46
Duct Drawing probe length 200
Duct Probe diameter 15
Separate probe Enclosure width/height 100/80
Separate probe Probe length/diameter 213/15

Select mounting arrangement, humidity output, temperature output or passive sensor, calibrated temperature range and display. Analog temperature outputs require a range selection; digital and passive versions follow their own configuration. Specifications and dimensions shown follow the manufacturer’s individual LFH10 specification. Supply minima differ between document revisions; the listed current-output values use the higher minima in its technical table. Confirm the delivered version, load and wiring before connection. Use an isolated supply for AC operation. Maintain non-condensing conditions; prolonged exposure to concentrated chemical gases may cause sensor drift. The main photo shows the wall-mounted configuration. Other family configurations require separate specification confirmation.