Dimensions and Structure

Thermostatic Expansion Valve
Thermostatic expansion valve for controlling liquid refrigerant supply to dry evaporators by sensing outlet superheat. Internal- and external-equalization versions use a remote sensing bulb and replaceable orifice components.
Valve Selection
| Catalog reference | Refrigerant | Equalization | Capillary (m) | Inlet option | Outlet option | Equalizer option |
|---|---|---|---|---|---|---|
| LFTX2 | R22 | Internal | 1.5 | 3/8 in / 10 mm | 1/2 in / 12 mm | — |
| LFTEX2 | R22 | External | 1.5 | 3/8 in / 10 mm | 1/2 in / 12 mm | 1/4 in / 6 mm |
| LFTZ2 | R407C | Internal | 1.5 | 3/8 in / 10 mm | 1/2 in / 12 mm | — |
| LFTEZ2 | R407C | External | 1.5 | 3/8 in / 10 mm | 1/2 in / 12 mm | 1/4 in / 6 mm |
| LFTN2 | R134a | Internal | 1.5 | 3/8 in / 10 mm | 1/2 in / 12 mm | — |
| LFTEN2 | R134a | External | 1.5 | 3/8 in / 10 mm | 1/2 in / 12 mm | 1/4 in / 6 mm |
| LFTS2 | R404A / R507 | Internal | 1.5 | 3/8 in / 10 mm | 1/2 in / 12 mm | — |
| LFTES2 | R404A / R507 | External | 1.5 | 3/8 in / 10 mm | 1/2 in / 12 mm | 1/4 in / 6 mm |
Operating Specifications
| Item | Value |
|---|---|
| Medium | Common HCFC and HFC refrigerants; select the matching refrigerant configuration |
| Ambient temperature | −40 to +60 °C |
| Evaporation temperature | −40 to +10 °C |
| Maximum working pressure | 46 bar |
| External equalizer connection | 1/4 in ODF or 6 mm ODF |
| Installation | Valve head upwards; observe the inlet-to-outlet flow direction |
Nominal Orifice Capacity (kW)
| Orifice | R22 | R407C | R134a | R404A / R507 |
|---|---|---|---|---|
| 0X | 0.5 | 0.5 | 0.4 | 0.38 |
| 00 | 1.0 | 1.1 | 0.9 | 0.7 |
| 01 | 2.5 | Confirm | 1.8 | 1.6 |
| 02 | Confirm | 3.8 | 2.6 | 2.1 |
| 03 | 5.2 | 5.6 | 4.8 | 4.2 |
| 04 | 8.0 | 8.6 | 6.7 | 6.0 |
| 05 | 10.5 | 11.3 | 8.6 | 7.7 |
| 06 | 15.5 | 16.7 | 10.5 | 9.1 |
Select the refrigerant, equalization arrangement, connection option and orifice together. Inch and metric connections are alternatives. Nominal capacities reproduce the supplier kW table; final duty selection requires operating-condition confirmation. Cells marked Confirm require a confirmed capacity before ordering. The product photograph shows one configuration; an external equalizer connection is required on external-equalization versions.