DODOMACH PNEUMATIC

Sensors & Instrumentation

Differential Temperature Controller

Mechanical differential temperature controller with two remote sensing bulbs. One bulb provides a reference and the controller switches according to the temperature difference between the two sensing points.

Dimensions and Structure

Differential Temperature Controller dimensions

Differential Temperature Controller

Mechanical differential temperature controller with two remote sensing bulbs. One bulb provides a reference and the controller switches according to the temperature difference between the two sensing points.

Differential Selection

Catalog reference Difference setting range (°C) Switching differential at minimum setting (°C) Operating temperature range (°C) Maximum bulb temperature (°C)
TSD40 0–15 ≤3 −25 to +40 60
TSD100 5–25 ≤5 20–100 150

General Specifications

Item Value
Ambient temperature −20 to +70 °C
Cable-entry hole diameter 15 mm
Sensing elements Two remote bulbs; reference and controlled temperature
Contact arrangement Changeover contact, see original diagram

Electrical Ratings

Load 110 V AC 220 V AC
Non-inductive 20 A 10 A
Inductive, full load 15 A 8 A
Inductive, instantaneous 72 A 72 A

Drawing Dimensions

Feature Dimension (mm)
Housing width 80
Housing depth 49
Housing height 63
Bulb length 120
Bulb diameter 12
Capillary diameter shown 2.5

Select the differential setting range and operating temperature range. The stated switching differential applies at the minimum differential setting. The two bulbs measure a temperature difference; they do not provide two independent temperature controls. Use the contact diagram for the selected version and confirm reset requirements.