Wall-mounted transmitter for measuring carbon monoxide in indoor air and ventilation systems. An electrochemical sensor converts CO concentration to a selected current, voltage or RS485/Modbus signal for monitoring applications such as equipment spaces and underground parking areas.
Specifications below apply to the LFG101 wall-mounted configuration.
Measurement and Operating Specifications
| Item | Specification |
|---|---|
| Measured gas | Carbon monoxide (CO) in air |
| Sensing principle | Electrochemical |
| Measuring ranges | 0–500 ppm or 0–1000 ppm |
| Accuracy | ±5% FS at 25 °C |
| Response time | T90 ≤15 s |
| Working temperature | −10 to +50 °C |
| Working humidity | 15–90% RH; non-condensing |
| Working pressure | 1 atm ±10% |
| Protection designation | IP6X; water-ingress rating unspecified |
Output and Supply Options
| Code | Output | Wiring | Supply |
|---|---|---|---|
| A4 | 4–20 mA | 3-wire | 10–30 VDC |
| V0 | 0–5 V | 3-wire | 10–30 VDC |
| V10 | 0–10 V | 3-wire | 16–30 VDC |
| RS | RS485/Modbus | 4-wire | 10–30 VDC |
Range Selection
| Code | Range |
|---|---|
| 1 | 0–500 ppm |
| 2 | 0–1000 ppm |
Dimensions
| Item | Value |
|---|---|
| Enclosure width | 100 mm |
| Enclosure height | 80 mm |
| Overall height shown | 110 mm |
| Depth | 46 mm |
| Horizontal mounting spacing | 88 mm |
| Probe diameter | 15 mm |
| Cable gland designation | M16 |
Dimensions Drawing
Ordering Information
Specify the LFG101 wall-mounted configuration, range code and output code from the tables. Confirm the complete ordering designation and supply for the selected version.
Select the concentration range and output, and match the supply to the chosen version. The 0–10 V version requires at least 16 VDC. Confirm wiring, calibration and sensor service requirements for the delivered unit; keep the sensing inlet unobstructed and avoid condensation or prolonged exposure above the measuring range. IP6X does not specify water-ingress protection. The photograph and dimensions show the wall-mounted configuration. Display and relay-equipped versions require their own configuration data.