DODOMACH PNEUMATIC

Sensors & Instrumentation

Infrared Carbon Dioxide Transmitter

Wall-mounted infrared transmitter for measuring carbon dioxide concentration in air. Selected current, voltage or RS485/Modbus output supports indoor air monitoring and ventilation applications.

Wall-mounted infrared transmitter for measuring carbon dioxide concentration in air. Selected current, voltage or RS485/Modbus output supports indoor air monitoring and ventilation applications.

Specifications below apply to the LFG201 legacy wall-mounted, single-output configuration. Revised and alternative configurations require separate confirmation.

Measurement and Operating Specifications

Item Specification
Measured gas Carbon dioxide (CO2) in air
Sensing principle Infrared absorption
Measuring ranges 0–2000 ppm, 0–5000 ppm or 0–10000 ppm
Accuracy at 25 °C ±(40 ppm + 3% of full scale)
Warm-up 2 min for operation; 10 min for maximum accuracy
Working temperature −10 to +50 °C
Working humidity 0–80% RH; non-condensing
Protection designation IP6X; water-ingress rating unspecified

Output and Supply Options

Code Output Wiring Supply
A4 4–20 mA 3-wire 10–30 VDC
V0 0–5 V 3-wire 10–30 VDC
V10 0–10 V 3-wire 16–30 VDC
RS RS485/Modbus 4-wire 10–30 VDC

Range Selection

Code Range
1 0–2000 ppm
2 0–5000 ppm
3 0–10000 ppm

Dimensions

Item Value
Enclosure width 100 mm
Enclosure height 80 mm
Overall height shown 110 mm
Depth 46 mm
Horizontal mounting spacing 88 mm
Probe diameter 15 mm
Cable gland designation M16

Dimensions Drawing

LFG201 wall-mounted CO2 transmitter dimensions

Ordering Information

Specify the LFG201 wall-mounted configuration, measuring-range code and output code from the tables. Confirm the complete ordering designation and delivered revision before ordering.

Select the measuring range and output together. The 0–10 V option requires at least 16 VDC. Allow 2 minutes for operation and 10 minutes for maximum accuracy. Specifications and dimensions describe the wall-mounted configuration shown; duct-mounted, display-equipped and revised versions require their own data. Confirm the delivered output and wiring before connection. Avoid condensation and keep the sensing inlet clear. IP6X does not specify water-ingress protection.