Configurable air quality transmitter combining selected temperature, relative humidity, carbon dioxide, particulate, VOC and formaldehyde channels. RS485/Modbus output supports distributed indoor monitoring, with optional display and status indicator on the wall-mounted version.
The illustrated LFG601 indoor wall-mounted configuration has a display. Sensing channels, display and indicator are selected options, not standard on every unit.
Optional Temperature and Humidity Channels
| Item | Temperature | Relative humidity |
|---|---|---|
| Sensor | Digital temperature/humidity sensor | Digital temperature/humidity sensor |
| Range | 0–50 °C | 0–100% RH |
| Accuracy | ±0.5 °C at 20 °C; within ±1 °C over 0–50 °C | Typical ±3% RH at 20 °C and 20–80% RH |
| Response at 20 °C, slow-moving air | 10–30 s | ≤10 s |
Optional Particulate Channels
| Item | Specification |
|---|---|
| Sensor | Laser particulate sensor; detection size 0.3–10 µm |
| PM2.5 range | 0–500 µg/m³; particle size 0.3–2.5 µm |
| PM10 range | 0–600 µg/m³; particle size 0.3–10 µm |
| PM2.5 low-band accuracy | ±10 µg/m³ over 0–100 µg/m³ at 25 °C |
| Resolution | 1 µg/m³ |
| Response in continuous mode | Single response <1 s; overall response <10 s |
Optional Carbon Dioxide Channel
| Item | Specification |
|---|---|
| Sensor | NDIR with ABC function |
| Range | 0–5000 ppm |
| Accuracy | ±(40 ppm + 3% of measured value) |
| Response time | T90: 2 min |
Optional VOC and Formaldehyde Channels
| Item | VOC | Formaldehyde |
|---|---|---|
| Sensor | Metal oxide semiconductor | Electrochemical |
| Range | 0–2 ppm | 0–1 ppm |
| Resolution | 1 ppb | Not specified |
| Accuracy | Not specified | ±10% FS at 25 °C |
| Warm-up / response | First power-up: 1 h; normal preheat: 3 min | T90 <120 s |
General Specifications
| Item | Specification |
|---|---|
| Supply | 12–36 VDC or 24 VAC ±20% |
| AC power condition | Isolated 24 VAC supply required |
| Output | RS485/Modbus; isolated or non-isolated version |
| Working environment | 0–50 °C; 0–95% RH, non-condensing |
| Storage environment | −20 to +60 °C; 0–95% RH, non-condensing |
| Protection | IP30 |
| Mounting | Indoor wall or ceiling configuration |
| Display and buttons | Optional for indoor wall version |
| Status indicator | Optional three-color LED for indoor wall version |
| Indoor housing / weight | PC; 148 g |
| Ceiling housing / weight | ABS; 235 g |
Channel and Installation Selection
| Field | Code | Option |
|---|---|---|
| Mounting | 1 / 2 | Indoor wall / ceiling |
| Temperature and humidity | 0 / 1 | Not fitted / fitted |
| Carbon dioxide | 0 / 1 | Not fitted / fitted |
| Particulate matter | 0 / 1 | Not fitted / PM2.5 and PM10 |
| VOC | 0 / 1 | Not fitted / fitted |
| Formaldehyde | 0 / 1 | Not fitted / fitted |
| Output | RS0 / RS1 | Non-isolated RS485 / isolated RS485 |
| Display and buttons | D / N | With / without; indoor version only |
| Three-color indicator | L / N | With / without; indoor version only |
Indoor Wall-Mounted Dimensions
| Item | Value |
|---|---|
| Width | 86 mm |
| Height | 115 mm |
| Overall depth shown | 27.5 mm |
| Body depth shown | 26.5 mm |
| Horizontal mounting spacing | 60 mm |
| Vertical mounting spacing | 30 mm |
Dimensions Drawing
Ordering Information
Specify the LFG60 family, mounting type, sensing-channel groups, RS485 isolation, display/buttons and indicator options using the selection table. Confirm the complete ordering designation and required channels for the delivered unit.
Order only the sensing channels required; not every unit includes all seven measurements. Temperature/humidity and PM2.5/PM10 are selected as paired groups. The photograph and drawing show the indoor wall-mounted configuration with display and buttons. Ceiling-mounted versions have different dimensions and do not use these display options. Use isolated 24 VAC power when operating on AC. VOC requires 1 hour at initial power-up and 3 minutes for normal preheating. Confirm particulate accuracy outside the stated PM2.5 low band for the selected configuration. Avoid condensation and keep sampling openings unobstructed.