DODOMACH PNEUMATIC

Sensors & Instrumentation

Thermal Air Velocity Transmitter

Thermal air velocity transmitter with a MEMS sensing probe for HVAC duct monitoring and ventilation applications. Select analog or RS485/Modbus output, duct or remote installation, and an optional local display.

Thermal air velocity transmitter with a MEMS sensing probe for HVAC duct monitoring and ventilation applications. Select analog or RS485/Modbus output, duct or remote installation, and an optional local display.

Specifications below apply to the LFS10 thermal configuration. The main photograph shows a duct-mounted unit without a display.

Measurement and Operating Specifications

Item Specification
Sensing principle MEMS thermal conduction / hot-film air velocity sensing
Ranges 0–10, 0–15, 0–20 or 0–30 m/s
Accuracy ±(0.2 m/s + 3% of measured value) at 20 °C, 45% RH and 1013 hPa
Resolution 0.01 m/s
Working temperature −10 to +60 °C
Storage temperature −20 to +80 °C
Protection Housing IP65; probe IP20
Housing / probe material PC / PA6
Display option LCD with units and backlight

Supply and Output

Item Specification
Supply 24 VAC/DC ±20%
Analog output 0–10 VDC / 4–20 mA, 3-wire
Digital option RS485/Modbus
Current output load ≤500 Ω
Voltage output load ≥2 kΩ
Analog range selection Selectable by jumper

Configuration Selection

Field Code Option
Output VI 0–10 VDC / 4–20 mA
Output RS RS485/Modbus
Installation 1 Duct-mounted
Installation 2 Remote probe
Display D With LCD
Display N Without LCD

Duct-Mounted Dimensions

Item Value
Housing width 100 mm
Housing height 80 mm
Housing depth 46 mm
Probe length shown 210 mm
Probe diameter 15 mm
Tip dimension shown 20 mm
Mounting flange hole spacing 60 mm
Mounting flange central opening 15.5 mm

Dimensions Drawing

LFS10 duct and remote configuration dimensions

Ordering Information

Specify the LFS10 configuration, measuring range, output code, installation code and display option from the tables. Confirm the complete ordering designation and required probe arrangement.

Specifications describe the standard thermal air velocity configuration. Select the measurement range and output before installation. IP65 applies to the housing; the sensing probe is rated IP20. The main photograph shows the duct-mounted version without display, while the dimension drawing also illustrates optional display and remote-probe arrangements. Lower-velocity versions require their own accuracy and load data. Do not use these specifications for pressure-derived or hazardous-area configurations.