Thermal air velocity transmitter with a MEMS sensing probe for HVAC duct monitoring and ventilation applications. Select analog or RS485/Modbus output, duct or remote installation, and an optional local display.
Specifications below apply to the LFS10 thermal configuration. The main photograph shows a duct-mounted unit without a display.
Measurement and Operating Specifications
| Item | Specification |
|---|---|
| Sensing principle | MEMS thermal conduction / hot-film air velocity sensing |
| Ranges | 0–10, 0–15, 0–20 or 0–30 m/s |
| Accuracy | ±(0.2 m/s + 3% of measured value) at 20 °C, 45% RH and 1013 hPa |
| Resolution | 0.01 m/s |
| Working temperature | −10 to +60 °C |
| Storage temperature | −20 to +80 °C |
| Protection | Housing IP65; probe IP20 |
| Housing / probe material | PC / PA6 |
| Display option | LCD with units and backlight |
Supply and Output
| Item | Specification |
|---|---|
| Supply | 24 VAC/DC ±20% |
| Analog output | 0–10 VDC / 4–20 mA, 3-wire |
| Digital option | RS485/Modbus |
| Current output load | ≤500 Ω |
| Voltage output load | ≥2 kΩ |
| Analog range selection | Selectable by jumper |
Configuration Selection
| Field | Code | Option |
|---|---|---|
| Output | VI | 0–10 VDC / 4–20 mA |
| Output | RS | RS485/Modbus |
| Installation | 1 | Duct-mounted |
| Installation | 2 | Remote probe |
| Display | D | With LCD |
| Display | N | Without LCD |
Duct-Mounted Dimensions
| Item | Value |
|---|---|
| Housing width | 100 mm |
| Housing height | 80 mm |
| Housing depth | 46 mm |
| Probe length shown | 210 mm |
| Probe diameter | 15 mm |
| Tip dimension shown | 20 mm |
| Mounting flange hole spacing | 60 mm |
| Mounting flange central opening | 15.5 mm |
Dimensions Drawing
Ordering Information
Specify the LFS10 configuration, measuring range, output code, installation code and display option from the tables. Confirm the complete ordering designation and required probe arrangement.
Specifications describe the standard thermal air velocity configuration. Select the measurement range and output before installation. IP65 applies to the housing; the sensing probe is rated IP20. The main photograph shows the duct-mounted version without display, while the dimension drawing also illustrates optional display and remote-probe arrangements. Lower-velocity versions require their own accuracy and load data. Do not use these specifications for pressure-derived or hazardous-area configurations.