Dimensions and Structure

Differential Temperature Controller
Mechanical differential temperature controller with two remote sensing bulbs. One bulb provides a reference and the controller switches according to the temperature difference between the two sensing points.
Differential Selection
| Catalog reference | Difference setting range (°C) | Switching differential at minimum setting (°C) | Operating temperature range (°C) | Maximum bulb temperature (°C) |
|---|---|---|---|---|
| TSD40 | 0–15 | ≤3 | −25 to +40 | 60 |
| TSD100 | 5–25 | ≤5 | 20–100 | 150 |
General Specifications
| Item | Value |
|---|---|
| Ambient temperature | −20 to +70 °C |
| Cable-entry hole diameter | 15 mm |
| Sensing elements | Two remote bulbs; reference and controlled temperature |
| Contact arrangement | Changeover contact, see original diagram |
Electrical Ratings
| Load | 110 V AC | 220 V AC |
|---|---|---|
| Non-inductive | 20 A | 10 A |
| Inductive, full load | 15 A | 8 A |
| Inductive, instantaneous | 72 A | 72 A |
Drawing Dimensions
| Feature | Dimension (mm) |
|---|---|
| Housing width | 80 |
| Housing depth | 49 |
| Housing height | 63 |
| Bulb length | 120 |
| Bulb diameter | 12 |
| Capillary diameter shown | 2.5 |
Select the differential setting range and operating temperature range. The stated switching differential applies at the minimum differential setting. The two bulbs measure a temperature difference; they do not provide two independent temperature controls. Use the contact diagram for the selected version and confirm reset requirements.