DODOMACH PNEUMATIC

FLUID VALVE

Differential Pressure Electrical Controller

Water-system differential-pressure controller with enclosed SPDT switch, direct-reading setting scale and multiple pressure-control configurations.

Dimensions and Structure

Differential Pressure Electrical Controller dimensions

Differential Pressure Electrical Controller

Differential-pressure electrical controller for monitoring the pressure difference between supply and return lines in water systems. The enclosed SPDT switch provides a control contact for a compatible external control circuit.

Pressure Control Configurations

Configuration Adjustment range or fixed setting (MPa) Switch differential (MPa) Set cut-off differential pressure (MPa) Maximum working pressure (MPa)
Without delay 0.05-0.15 >=0.05 0.05 1.70
Without delay 0.05-0.20 >=0.05 0.05 1.70
Without delay 0.05-0.35 >=0.05 0.10 1.70
Without delay 0.10-0.60 >=0.05 0.10 3.30
With delay 0.05-0.35 >=0.05 0.10 1.70
With delay 0.10-0.60 >=0.05 0.10 3.30
With delayed reverse contact 0.05-0.35 >=0.05 0.10 1.70
With delayed reverse contact 0.10-0.60 >=0.05 0.10 3.30
Manual fixed differential pressure 0.15 >=0.04 0.15 3.30
Manual fixed differential pressure 0.25 >=0.04 0.25 3.30

Dimensions

L (mm) W (mm) H (mm) b (mm)
150 63 80.6 12

Construction and Operation

Item Specification
Application Differential-pressure control between water-system supply and return lines
Switch arrangement Single-pole double-throw (SPDT), enclosed switch
Setting indication Direct-reading scale
Materials listed for assembly Plastic, stainless steel and brass; component grades require confirmation
Controller rear mounting Four M4 mounting holes; optional mounting bracket
Electrical contact rating and delay time Confirm for selected configuration
Operating temperature and fluid compatibility Confirm for selected configuration

Select the required pressure configuration before ordering. Pressure adjustment, switch differential and maximum working pressure are separate specifications. Dimensions follow the source table; the b label is retained without assigning a connection thread. Confirm electrical contact rating, wiring, delay duration where applicable, operating temperature and fluid compatibility before installation.