Dimensions and Structure

Electric Two-Way Stainless Steel Regulating Valve
Electric two-way stainless steel regulating valve for heating and air-conditioning control applications. The source lists DN15-DN50 sizes with on/off, modulating and differential-pressure control packages. Valve dimensions and service data are separated from the reference actuator specifications.
Dimensions
| DN | L (mm) | D (mm) | A (mm) | H (mm) |
|---|---|---|---|---|
| 15 | 83 | 94 | 46.5 | 287 |
| 20 | 83 | 94 | 46.5 | 287 |
| 25 | 103 | 94 | 56 | 291 |
| 32 | 110 | 94 | 50 | 296 |
| 40 | 122 | 94 | 50 | 298 |
| 50 | 131 | 94 | 57 | 303 |
Materials and Service
| Parameter | Specification |
|---|---|
| Body, cover, disc and stem | Stainless steel |
| Seal | NBR |
| Medium | Hot or cold water; 50% ethylene glycol |
| Medium temperature | 5-95 C |
| Flow characteristic options | Equal percentage or linear |
| Leakage stated in source | 0.01% of Kv |
Reference 24 VAC Actuator
| Parameter | Specification |
|---|---|
| Rated supply | 24 VAC +/-10%; 50/60 Hz |
| Voltage control signal | 0-10 VDC |
| Voltage feedback signal | 0-10 VDC |
| Full-stroke time | 180 seconds |
| Actuator weight | 0.8 kg |
| Housing | Flame-retardant ABS engineering plastic |
Control Package Options
| Package | Supply options | Additional equipment listed |
|---|---|---|
| On/off, two-piece set | 220 VAC or 24 VAC | Not listed |
| Modulating, two-piece set | 220 VAC or 24 VAC | Not listed |
| Differential-pressure, four-piece set | 24 VAC | Differential-pressure device; transformer |
| Modulating, five-piece set | 24 VAC | Transformer; sensor; temperature controller |
The actuator table describes the 24 VAC reference configuration, not every actuator pictured or the 220 VAC package. The source photograph and technical table differ in force, ambient limits and supply details; force and ambient ratings are therefore withheld. Power consumption and current-signal ranges also require confirmation. The original structure drawing carries PN25, whereas the service table states 1600 kPa; the drawing is retained for dimensional reference and does not establish a confirmed pressure rating. Confirm pressure and actuator configuration before selection. No numeric Kv schedule or thread standard is supplied. Package equipment is listed for selection, not as a statement that all accessories are included.