DODOMACH PNEUMATIC

Sensors & Instrumentation

Electrochemical Carbon Monoxide Transmitter

Wall-mounted transmitter for measuring carbon monoxide in indoor air and ventilation systems. An electrochemical sensor converts CO concentration to a selected current, voltage or RS485/Modbus signal for monitoring applications such as equipment spaces and underground parking areas.

Wall-mounted transmitter for measuring carbon monoxide in indoor air and ventilation systems. An electrochemical sensor converts CO concentration to a selected current, voltage or RS485/Modbus signal for monitoring applications such as equipment spaces and underground parking areas.

Specifications below apply to the LFG101 wall-mounted configuration.

Measurement and Operating Specifications

Item Specification
Measured gas Carbon monoxide (CO) in air
Sensing principle Electrochemical
Measuring ranges 0–500 ppm or 0–1000 ppm
Accuracy ±5% FS at 25 °C
Response time T90 ≤15 s
Working temperature −10 to +50 °C
Working humidity 15–90% RH; non-condensing
Working pressure 1 atm ±10%
Protection designation IP6X; water-ingress rating unspecified

Output and Supply Options

Code Output Wiring Supply
A4 4–20 mA 3-wire 10–30 VDC
V0 0–5 V 3-wire 10–30 VDC
V10 0–10 V 3-wire 16–30 VDC
RS RS485/Modbus 4-wire 10–30 VDC

Range Selection

Code Range
1 0–500 ppm
2 0–1000 ppm

Dimensions

Item Value
Enclosure width 100 mm
Enclosure height 80 mm
Overall height shown 110 mm
Depth 46 mm
Horizontal mounting spacing 88 mm
Probe diameter 15 mm
Cable gland designation M16

Dimensions Drawing

Wall-mounted CO transmitter dimensions

Ordering Information

Specify the LFG101 wall-mounted configuration, range code and output code from the tables. Confirm the complete ordering designation and supply for the selected version.

Select the concentration range and output, and match the supply to the chosen version. The 0–10 V version requires at least 16 VDC. Confirm wiring, calibration and sensor service requirements for the delivered unit; keep the sensing inlet unobstructed and avoid condensation or prolonged exposure above the measuring range. IP6X does not specify water-ingress protection. The photograph and dimensions show the wall-mounted configuration. Display and relay-equipped versions require their own configuration data.