Dimensions and Structure

Flanged Self-Operated Differential Pressure Control Valve
Self-operated differential pressure control valve with flanged connections and a pressure-sensing tube. It regulates the pressure difference in circulating-water systems without an external power supply.
Flanged Configuration Dimensions and Flow Ranges
| DN | L (mm) | H (mm) | Flow range (m3/h) |
|---|---|---|---|
| 32 | 210 | 185 | 1-4 |
| 40 | 210 | 259 | 1.5-6 |
| 50 | 215 | 232 | 2-8 |
| 65 | 230 | 245 | 3-12 |
| 80 | 280 | 321 | 5-20 |
| 100 | 300 | 368 | 10-30 |
| 125 | 315 | 407 | 15-45 |
| 150 | 350 | 453 | 30-80 |
| 200 | 405 | 530 | 40-180 |
| 250 | 455 | 500 | 100-300 |
| 300 | 610 | 730 | 150-500 |
| 350 | 640 | 840 | 200-700 |
Pressure Control and Service
| Parameter | Specification |
|---|---|
| Operation | Self-operated differential-pressure control; no external power |
| Connection | Flanged |
| Medium | Water |
| Nominal pressure | 1.6 MPa |
| Working differential-pressure range | 0.03-0.3 MPa |
| Control differential-pressure setting listed in source | 0.03 MPa |
| Adjustable control differential-pressure range | 0.03-0.15 MPa |
| Pressure-sensing tube length | 1.0 m |
| Pressure-sensing tube connection | 1/2 inch pipe thread; confirm thread standard |
| Body/trim materials and medium-temperature rating | Configuration confirmation required |
This page covers only the flanged configuration. The source separates threaded DN15-DN25 from flanged DN32-DN350. Body/trim materials and temperature statements conflict within the source, so confirm the selected configuration before ordering. Flange diameter, thickness, bolt-circle and bolt-hole values are blank in the source and are not inferred. The 1/2 inch connection refers to the pressure-sensing tube, not the valve's main pipeline connection.