Dimensions and Structure

Electric Two-Way Brass Dynamic Balancing Regulating Valve
Electric two-way brass dynamic balancing regulating valve for heating and air-conditioning water circuits. The source lists DN32-DN65 dimensions, an NBR seal and selectable control packages. Original structure dimensions and reference actuator options are presented separately.
Dimensions
| DN | L (mm) | D (mm) | A (mm) | H (mm) |
|---|---|---|---|---|
| 32 | 104.6 | 94 | 64 | 260 |
| 40 | 113 | 94 | 70 | 289 |
| 50 | 124 | 94 | 66 | 295 |
| 65 | 151 | 94 | 72 | 300 |
Materials and Service
| Parameter | Specification |
|---|---|
| Body, cover, disc and stem | Brass |
| Seal | NBR |
| Medium | Hot or cold water; 50% ethylene glycol |
| Medium temperature | 5-95 C |
| Nominal pressure | 1600 kPa |
| Flow characteristic options | Equal percentage or linear |
| Leakage stated in source | 0.01% of Kv |
Reference 24 VAC Actuator Options
| Parameter | AC control option | Modulating option |
|---|---|---|
| Rated supply | 24 VAC +/-10%; 50/60 Hz | 24 VAC +/-10%; 50/60 Hz |
| Control signal | 24 VAC | 0-10 VDC or 0-10 mA |
| Feedback signal | None | 0-10 VDC or 0-10 mA |
| Output force | 1000 N | 1000 N |
| Full-stroke time | 90 seconds | 90 seconds |
| Weight stated in source | 1.2 kg | 4.6 kg |
| Storage temperature | -20 to 65 C | -20 to 65 C |
| Humidity | Non-condensing; numerical limit not stated | Below 90% RH, non-condensing |
| Bracket | Die-cast aluminium alloy | Die-cast aluminium alloy |
| Housing | Flame-retardant ABS engineering plastic | Flame-retardant ABS engineering plastic |
Control Package Options
| Package | Supply options | Additional equipment listed |
|---|---|---|
| On/off, two-piece set | 220 VAC or 24 VAC | Not listed |
| Modulating, two-piece set | 220 VAC or 24 VAC | Not listed |
| Differential-pressure, four-piece set | 24 VAC | Differential-pressure device; transformer |
| Modulating, five-piece set | 24 VAC | Transformer; sensor; temperature controller |
Materials and dimensions are transcribed from the corresponding valve table. Actuator data describe the 24 VAC reference options and do not establish ratings for every actuator or the 220 VAC packages. Photo and table power consumption and ambient limits differ, so these values are withheld. The photo states travel time per millimetre while the table lists full-stroke time; without a specified total stroke they must not be treated as equivalent. Confirm the selected actuator, signal range and weight before ordering. Balancing flow range, differential-pressure operating range, numeric Kv and thread standard are not supplied. Package accessories are selection options, not a statement that every accessory is included.