DODOMACH PNEUMATIC

FLUID VALVE

Electrothermal Two-Way Brass Dynamic Balancing Valve

Normally closed electrothermal brass dynamic balancing valve, DN20 and DN25, with 24, 110 or 220 VAC actuator variants.

Dimensions and Structure

Electrothermal Two-Way Brass Dynamic Balancing Valve dimensions

Electrothermal Two-Way Brass Dynamic Balancing Valve

Normally closed electrothermal two-way brass dynamic balancing valve for fan-coil and heating or air-conditioning water circuits. It combines dynamic balancing with electrically operated on/off control. The source lists DN20 and DN25 flow configurations and three actuator supply variants.

Dimensions for Source-Listed Flow Configurations

DN Flow configuration (m3/h) L (mm) D (mm) A (mm) W (mm) H (mm)
20 0.09-1.52 92 41 150 17.5 100
25 0.127-2.15 99 41 160 19 110

Flow Range Options

DN Option Flow range (m3/h) Operating differential pressure
20 1 0.09-1.52 Requires confirmation
20 2 0.11-1.76 Requires confirmation
20 3 0.127-2.15 Requires confirmation
20 4 0.22-3.52 Requires confirmation
25 1 0.09-1.52 Requires confirmation
25 2 0.11-1.76 Requires confirmation
25 3 0.127-2.15 Requires confirmation
25 4 0.22-3.52 Requires confirmation

Materials and Valve Service

Parameter Specification
Body and cover Brass
Disc EPDM
Stem Stainless steel
Seal NBR
Operation Normally closed, two-way
Medium Hot or cold water; 50% ethylene glycol
Medium temperature 5-95 C
Nominal pressure 1600 kPa
Flow characteristic options stated in source Equal percentage or linear
Leakage stated in source 0.01% of Kv

Electrothermal Actuator

Parameter Specification
Supply variants 220 VAC; 110 VAC; 24 VAC
Power consumption 3.5 VA
Stroke 3.5 mm
Thrust 110 N
Full-stroke time 6 minutes
Actuator mounting nut M30 x 1.5 mm
Operating ambient -5 to 60 C
Lead length 900 mm
Housing Flame-retardant PC
Protection IP54

The source differential-pressure column has an inconsistent unit and values relative to PN16, so operating differential-pressure ranges are withheld pending confirmation. Listed flow options must be selected with a confirmed pressure range. Dimensions are shown only against the flow rows where the source actually supplies them; they are not assumed to apply to every option. M30 x 1.5 mm describes the actuator mounting nut, not the pipe connection. Equal-percentage or linear wording is reproduced as a valve flow-characteristic option, not a claim of an electrical modulating signal. Confirm the required supply variant and connection standard before ordering.