Dimensions and Structure

Electrothermal Two-Way Brass Dynamic Balancing Valve
Normally closed electrothermal two-way brass dynamic balancing valve for fan-coil and heating or air-conditioning water circuits. It combines dynamic balancing with electrically operated on/off control. The source lists DN20 and DN25 flow configurations and three actuator supply variants.
Dimensions for Source-Listed Flow Configurations
| DN | Flow configuration (m3/h) | L (mm) | D (mm) | A (mm) | W (mm) | H (mm) |
|---|---|---|---|---|---|---|
| 20 | 0.09-1.52 | 92 | 41 | 150 | 17.5 | 100 |
| 25 | 0.127-2.15 | 99 | 41 | 160 | 19 | 110 |
Flow Range Options
| DN | Option | Flow range (m3/h) | Operating differential pressure |
|---|---|---|---|
| 20 | 1 | 0.09-1.52 | Requires confirmation |
| 20 | 2 | 0.11-1.76 | Requires confirmation |
| 20 | 3 | 0.127-2.15 | Requires confirmation |
| 20 | 4 | 0.22-3.52 | Requires confirmation |
| 25 | 1 | 0.09-1.52 | Requires confirmation |
| 25 | 2 | 0.11-1.76 | Requires confirmation |
| 25 | 3 | 0.127-2.15 | Requires confirmation |
| 25 | 4 | 0.22-3.52 | Requires confirmation |
Materials and Valve Service
| Parameter | Specification |
|---|---|
| Body and cover | Brass |
| Disc | EPDM |
| Stem | Stainless steel |
| Seal | NBR |
| Operation | Normally closed, two-way |
| Medium | Hot or cold water; 50% ethylene glycol |
| Medium temperature | 5-95 C |
| Nominal pressure | 1600 kPa |
| Flow characteristic options stated in source | Equal percentage or linear |
| Leakage stated in source | 0.01% of Kv |
Electrothermal Actuator
| Parameter | Specification |
|---|---|
| Supply variants | 220 VAC; 110 VAC; 24 VAC |
| Power consumption | 3.5 VA |
| Stroke | 3.5 mm |
| Thrust | 110 N |
| Full-stroke time | 6 minutes |
| Actuator mounting nut | M30 x 1.5 mm |
| Operating ambient | -5 to 60 C |
| Lead length | 900 mm |
| Housing | Flame-retardant PC |
| Protection | IP54 |
The source differential-pressure column has an inconsistent unit and values relative to PN16, so operating differential-pressure ranges are withheld pending confirmation. Listed flow options must be selected with a confirmed pressure range. Dimensions are shown only against the flow rows where the source actually supplies them; they are not assumed to apply to every option. M30 x 1.5 mm describes the actuator mounting nut, not the pipe connection. Equal-percentage or linear wording is reproduced as a valve flow-characteristic option, not a claim of an electrical modulating signal. Confirm the required supply variant and connection standard before ordering.