DODOMACH PNEUMATIC

Differential Pressure Transmitters

Thermal Low Differential Pressure Transmitter

Low differential pressure transmitter using a thermal sensing element and integrated micro-flow channel for dry air or neutral gas. Three bidirectional ranges cover low-pressure monitoring in HVAC, cleanrooms and process ventilation, with simultaneous current/voltage output or Modbus RTU communication.

Dimensions and Structure

Thermal differential pressure transmitter dimensions

Thermal Low Differential Pressure Transmitter

Low differential pressure transmitter using a thermal sensing element and integrated micro-flow channel for dry air or neutral gas. Three bidirectional ranges cover low-pressure monitoring in HVAC, cleanrooms and process ventilation, with simultaneous current/voltage output or Modbus RTU communication.

Range and Accuracy

Range code Differential pressure range (Pa) Accuracy
1 −25 to +25 ±1 Pa
2 −50 to +50 ±1% FS
3 −100 to +100 ±0.5% FS

Output and Power Supply

Output code Output Wiring Supply
A 4–20 mA and 0–10 V simultaneously Six-wire 12–30 VDC or 24 VAC ±20%
E RS485, Modbus RTU Four-wire 9–30 VDC or isolated 24 VAC ±20%
E1 Isolated RS485, Modbus RTU Four-wire 9–30 VDC or 24 VAC ±20%

Operating Specifications

Item Value
Sensing principle Thermal differential pressure sensing through an integrated micro-flow channel
Medium Dry air or neutral gas
Overload pressure 7 kPa
Burst pressure 20 kPa
Operating temperature −20 to +70 °C
Compensation temperature −10 to +60 °C
Storage temperature −40 to +80 °C
Protection IP65
Pressure connection Ø6.2 mm metal barbed ports
Cable maximum diameter 8 mm
Weight 200 g
Display options N: no display; O: display

Dimensions

Width (mm) Overall height (mm) Body height (mm) Depth (mm) Cable gland
100 103 80 46 M16

Select range, display and output together. Accuracy depends on the selected range. The 7 kPa overload and 20 kPa burst ratings are not measurement ranges. Non-isolated RS485 models require an isolated 24 VAC source when AC-powered. Confirm the ordered isolated RS485 configuration before installation. Catalog reference: LFM53; ordering structure: series – range – display – output.