DODOMACH PNEUMATIC

FLUID VALVE

Electric Two-Way Brass Dynamic Balancing Regulating Valve

Electric two-way brass dynamic balancing regulating valve, DN32-DN65, with NBR seal and selectable control packages.

Dimensions and Structure

Electric Two-Way Brass Dynamic Balancing Regulating Valve dimensions

Electric Two-Way Brass Dynamic Balancing Regulating Valve

Electric two-way brass dynamic balancing regulating valve for heating and air-conditioning water circuits. The source lists DN32-DN65 dimensions, an NBR seal and selectable control packages. Original structure dimensions and reference actuator options are presented separately.

Dimensions

DN L (mm) D (mm) A (mm) H (mm)
32 104.6 94 64 260
40 113 94 70 289
50 124 94 66 295
65 151 94 72 300

Materials and Service

Parameter Specification
Body, cover, disc and stem Brass
Seal NBR
Medium Hot or cold water; 50% ethylene glycol
Medium temperature 5-95 C
Nominal pressure 1600 kPa
Flow characteristic options Equal percentage or linear
Leakage stated in source 0.01% of Kv

Reference 24 VAC Actuator Options

Parameter AC control option Modulating option
Rated supply 24 VAC +/-10%; 50/60 Hz 24 VAC +/-10%; 50/60 Hz
Control signal 24 VAC 0-10 VDC or 0-10 mA
Feedback signal None 0-10 VDC or 0-10 mA
Output force 1000 N 1000 N
Full-stroke time 90 seconds 90 seconds
Weight stated in source 1.2 kg 4.6 kg
Storage temperature -20 to 65 C -20 to 65 C
Humidity Non-condensing; numerical limit not stated Below 90% RH, non-condensing
Bracket Die-cast aluminium alloy Die-cast aluminium alloy
Housing Flame-retardant ABS engineering plastic Flame-retardant ABS engineering plastic

Control Package Options

Package Supply options Additional equipment listed
On/off, two-piece set 220 VAC or 24 VAC Not listed
Modulating, two-piece set 220 VAC or 24 VAC Not listed
Differential-pressure, four-piece set 24 VAC Differential-pressure device; transformer
Modulating, five-piece set 24 VAC Transformer; sensor; temperature controller

Materials and dimensions are transcribed from the corresponding valve table. Actuator data describe the 24 VAC reference options and do not establish ratings for every actuator or the 220 VAC packages. Photo and table power consumption and ambient limits differ, so these values are withheld. The photo states travel time per millimetre while the table lists full-stroke time; without a specified total stroke they must not be treated as equivalent. Confirm the selected actuator, signal range and weight before ordering. Balancing flow range, differential-pressure operating range, numeric Kv and thread standard are not supplied. Package accessories are selection options, not a statement that every accessory is included.