Dimensions and Structure

HVAC Temperature Sensor Probe
HVAC temperature sensor with a stainless-steel probe and flame-retardant ABS enclosure. NTC thermistor, platinum-resistance and nickel-resistance elements are listed as separate options for compatible temperature-control equipment.
Sensor Element Options
| Element option | Measurement range (deg C) | Source-listed accuracy or reference |
|---|---|---|
| NTC thermistor | -70 to 150 | +/-0.5 K |
| Platinum resistance | -70 to 200 | +/-0.2 K |
| Nickel resistance | -60 to 200 | DIN 43760 listed; tolerance class requires confirmation |
Environment and Construction
| Item | Specification |
|---|---|
| Application | Air temperature in ducts and water temperature in pipes, with suitable installation accessories |
| Operating ambient temperature | -40 to 70 deg C |
| Operating humidity | <95% RH |
| Storage temperature | -40 to 80 deg C |
| Storage humidity | <95% RH |
| Cover and mounting base | Flame-retardant ABS plastic |
| Probe | Stainless steel |
| Protection rating listed | IP56 |
| Terminal connection size listed | 2.5 mm2; confirm compatible cable size |
| Overall dimensions and insertion length | Confirm selected configuration; source outline does not provide numeric dimensions |
Select the sensing element, resistance characteristic, insertion length and installation accessories to suit the control system. Probe measurement ranges are separate from the enclosure ambient limits. Confirm the selected dimensions, terminal arrangement, cable size and calibration requirements before installation. The outline is provided for structure reference; numeric dimensions are not specified in the source.