Dimensions and Structure

Magnetic Diaphragm Refrigeration Check Valve
Inline magnetic diaphragm check valve for refrigeration systems, preventing reverse refrigerant flow with a flexible sealing element and an integrated filter. The guided design permits installation in different orientations while maintaining the indicated flow direction.
Selection and Dimensions
| Catalog reference | ODF (in) | D (mm) | L (mm) | Filter (mesh) | Maximum working pressure (kPa) | R404A liquid capacity (kW) |
|---|---|---|---|---|---|---|
| LFDCV-4 | 1/4 | 22 | 102 | 40 | 5500 | 6.8 |
| LFDCV-6 | 3/8 | 22 | 102 | 40 | 5500 | 14.2 |
| LFDCV-8 | 1/2 | 29 | 127 | 40 | 5200 | 38.2 |
| LFDCV-10 | 5/8 | 29 | 127 | 40 | 5200 | 42.6 |
| LFDCV-12 | 3/4 | 41 | 178 | 40 | 4100 | 79.7 |
| LFDCV-14 | 7/8 | 41 | 178 | 40 | 4100 | 108.5 |
| LFDCV-18 | 1-1/8 | 54 | 213 | 40 | 4000 | 188.5 |
| LFDCV-22 | 1-3/8 | 67 | 238 | 40 | 4000 | 232.8 |
| LFDCV-26 | 1-5/8 | 80 | 267 | 40 | 3000 | 397.7 |
| LFDCV-34 | 2-1/8 | 92 | 305 | 40 | 3000 | 691.1 |
| LFDCV-42 | 2-5/8 | 105 | 330 | 40 | 3000 | 927.3 |
| LFDCV-50 | 3-1/8 | 105 | 330 | 40 | 3000 | 1262.5 |
Operating Specifications
| Item | Value |
|---|---|
| Valve principle | Magnetic diaphragm with flexible sealing |
| Medium examples | R22, R134a, R410A and refrigerant oil |
| Working temperature | −40 to +120 °C |
| Installation orientation | Any orientation; follow the flow arrow |
| Filter | Integrated 40-mesh screen |
| Connection | ODF solder |
Select the connection size and use its individual maximum working pressure from the table. The 5.5 MPa family maximum does not apply to every size. R404A liquid capacities are supplier catalog figures; confirm design conditions and opening differential for the intended duty. The photograph illustrates the family and does not identify a particular connection size.