Dimensions and Structure

Thermal Low Differential Pressure Transmitter
Low differential pressure transmitter using a thermal sensing element and integrated micro-flow channel for dry air or neutral gas. Three bidirectional ranges cover low-pressure monitoring in HVAC, cleanrooms and process ventilation, with simultaneous current/voltage output or Modbus RTU communication.
Range and Accuracy
| Range code | Differential pressure range (Pa) | Accuracy |
|---|---|---|
| 1 | −25 to +25 | ±1 Pa |
| 2 | −50 to +50 | ±1% FS |
| 3 | −100 to +100 | ±0.5% FS |
Output and Power Supply
| Output code | Output | Wiring | Supply |
|---|---|---|---|
| A | 4–20 mA and 0–10 V simultaneously | Six-wire | 12–30 VDC or 24 VAC ±20% |
| E | RS485, Modbus RTU | Four-wire | 9–30 VDC or isolated 24 VAC ±20% |
| E1 | Isolated RS485, Modbus RTU | Four-wire | 9–30 VDC or 24 VAC ±20% |
Operating Specifications
| Item | Value |
|---|---|
| Sensing principle | Thermal differential pressure sensing through an integrated micro-flow channel |
| Medium | Dry air or neutral gas |
| Overload pressure | 7 kPa |
| Burst pressure | 20 kPa |
| Operating temperature | −20 to +70 °C |
| Compensation temperature | −10 to +60 °C |
| Storage temperature | −40 to +80 °C |
| Protection | IP65 |
| Pressure connection | Ø6.2 mm metal barbed ports |
| Cable maximum diameter | 8 mm |
| Weight | 200 g |
| Display options | N: no display; O: display |
Dimensions
| Width (mm) | Overall height (mm) | Body height (mm) | Depth (mm) | Cable gland |
|---|---|---|---|---|
| 100 | 103 | 80 | 46 | M16 |
Select range, display and output together. Accuracy depends on the selected range. The 7 kPa overload and 20 kPa burst ratings are not measurement ranges. Non-isolated RS485 models require an isolated 24 VAC source when AC-powered. Confirm the ordered isolated RS485 configuration before installation. Catalog reference: LFM53; ordering structure: series – range – display – output.